UPS power supply Ubiquiti UPS-2U-EU 1500VA/1000W (230V, 2xGbE, 2x12V 9Ah, 4xC13, IP20)
-
- General
- Dimensions442.4 x 300 x 87.4 mm (17.4 x 11.8 x 3.4")
- Weight13.7 kg (30.2 lb)
- Enclosure MaterialGalvanized steel
- Form FactorRack mount (2U)
- WeatherproofingIP20
- ManagementEthernet
- Networking Interface(1) 100/10 MbE port for network connection, (2) GbE ports for surge in/out
- Power Inputs(1) OVC II AC in: C14 socket, 1.8 m (5.9 ft) removable power cord
- Power Outputs(4) Battery backup/surge protection: C13, (4) Surge protection: C13
- Capacity1,500VA / 1,000W
- UPS TypeLine interactive
- Input Voltage Range170—280V AC
- Power Method(1) TN system, 220—240V AC, 10A Max., 50/60 Hz
- Nominal Input Voltage230V AC
- Output Voltage220—240V AC
- Nominal Output Voltage230V AC
- Frequency RangeAC mode: 50/60 Hz ±5 Hz (Auto sensing), Battery mode: 50 Hz ±1 Hz
- AC Voltage Regulation±10% (Battery mode)
- Transfer Time6 ms typical; 10 ms max. (Battery mode)
- Waveform (Battery Mode)Simulated sine wave
- Battery Type(2) Lead Acid 12V, 9Ah
- Runtime at Full Load2.3 minutes
- Runtime at Half Load8 minutes
- Battery Charging Time6–8 hours to 90% capacity
- Overload Protection (Online Mode)110% for 5 min then fault, 120% immediate fault
- Overload Protection (Battery Mode)110% shutdown in 5 sec, 120% shutdown immediately
- Short Circuit Protection (Online Mode)Breaker, 250V AC, 10A
- Output Short-Circuit CurrentIpeak: 444.0A, Irms: 223.1A
- Buttons(1) Power, (1) Factory reset
- LEDsStatus indicators: Off, Flashing white, Steady white, Steady blue, Flashing blue, Alternating white/blue, Rapid flashing blue, Steady red, Flashing red
- Operating Altitude3,000 m (1.9 mi)
- Operating EnvironmentPollution Degree 2
- Ambient Storage Temperature-20 to 50° C (-4 to 122° F)
- Ambient Operating Temperature0 to 40° C (32 to 104° F)
- Ambient Operating Humidity0 to 95% noncondensing
- CertificationsCE, IEC 62040-1