Smoke detector Apollo ORBIS MARINE (ORB-OP-42001-MAR)
ManufacturerApollo-
General Applications - Bedrooms
- Escape routes
- Marine
Fire Type Slow burning, smouldering fires Warranty 10 year Performance Chamber type Chevron Electrical Maximum power-up time <20 seconds Quiescent current 95μA Quiescent current tested at 24V dc Sampling frequency Once every 4 seconds Polarity L1 & L2 are polarity sensitive Minimum 'detector active' voltage 6V Holding voltage (min) 5V Holding voltage (max) 33V Holding voltage 5 to 33V Minimum voltage to light alarm LED 5V Alarm reset voltage <1V Alarm reset time 1s Alarm load 600Ω Environmental Humidity (min) 0% RH Humidity (max) 98% RH Humidity Note no condensation or icing Humidity 0% to 98% (no condensation or icing) Operating temperature (min) -40°C Operating temperature (max) 70°C Operating temperature -40 to 70°C IP rating Value IP23D Storage temperature (min) -40°C Storage temperature (max) 70°C Storage temperature -40 to 70°C Conformance Approvals - BV
- LR
- DNV.GL
- CCS
- KRS
- ABS
- MED
Mechanical Weight 75g Colour White Materials housing Polycarbonate Product length 31mm Product diameter 97mm Detection principle Photo-electric light scattering. Sensor configuration Chamber with surface-mount infrared emmiter and prism. Solid state integrated photo-diode and amplifier.