Products catalog

  • Residual Current Circuit Breaker with Overcurrent Protection Hager ADM470C (4P, 20A, Type A, 30mA, 6kA)

    • Architecture
    • Type of pole4P
    • Number of protected poles4
    • CurveC
    • Safety
    • Residual current typeA
    • Ingress Protection (IP) classIP2X
    • Main electrical attributes
    • Rated short-circuit breaking capacity Icn AC according to IEC 60898-16 kA
    • Voltage
    • Rated insulation voltage Ui500 V
    • Rated impulse withstand voltage Uimp4,000 V
    • Rated operational voltage Ue230 - 400 V
    • Overvoltage category according to IEC 60947-13
    • Type voltage supplyAC
    • Dielectric strength value of power frequency2 kV
    • Electric current
    • Rated current20 A
    • Rated residual operating current Idn30 mA
    • Rated current -25°C23.80 A
    • Rated current at -20°C23.50 A
    • Rated current -15°C23.20 A
    • Rated current -10°C22.90 A
    • Rated current -5°C22.50 A
    • Rated current at 0°C22.20 A
    • Rated current 5°C21.80 A
    • Rated current 10°C21.50 A
    • Rated current 15°C21.10 A
    • Rated current at 20°C20.80 A
    • Rated current 25°C20.40 A
    • Rated current 30°C20 A
    • Rated current 35°C19.60 A
    • Rated current at 40°C19.10 A
    • Rated current at 45°C18.60 A
    • Rated current at 50°C18.20 A
    • Rated current 55°C17.70 A
    • Rated current 60°C17.20 A
    • Correction factor of rating current for 2 devices placed side by side0.80
    • Min./max. threshold value of the AC thermal operation1.13 - 1.45 A
    • Rated service breaking capacity Ics AC according to IEC 60898-16 kA
    • Power
    • Total power loss under IN11.70 W
    • Frequency
    • Frequency50 - 50 Hz
    • Installation, mounting
    • Nominal tightening torque down terminal2 - 2 Nm
    • Nominal tightening torque top terminal2 - 2 Nm
    • Type of bottom connection for modular devicesbiconnect
    • Use conditions
    • Max. altitude2,000 m
    • Class of energy limitation I²t3
    • Operating temperature-25 - 40 °C
    • Storage/transport temperature-55 - 70 °C
    • Degree of pollution according to IEC 60664 / IEC 60947-22
    • Endurance
    • Electric endurance in number of cycles2,000
    • Number of mechanical operations4,000
    • Connection
    • Cross-section of input with screws, for flexible conductors1 - 16 mm²
    • Cross-section of input with screws, for massive conductors1 - 25 mm²
    • Cross-section of input and output with screws, for flexible conductors1 - 16 mm²
    • Cross-section of input and output with screws, for massive conductors1 - 25 mm²
    • Capacity
    • Number of modules4
    • Dimensions
    • Height84 mm
    • Width71 mm
    • Depth70 mm