Residual current circuit breaker with overcurrent protection Hager AD966J (2P, 16A, C, type AC, 1P+N, 6kA)
-
- General
- Pole configuration1P+N
- Tripping curveC
- Rated current16 A
- Rated residual operating current Idn30 mA
- Rated current at –25 °C18.50 A
- Rated current at –20 °C18.30 A
- Rated current at –15 °C18.10 A
- Rated current at –10 °C17.90 A
- Rated current at –5 °C17.70 A
- Rated current at 0 °C17.40 A
- Rated current at 5 °C17.20 A
- Rated current at 10 °C17.00 A
- Rated current at 15 °C16.70 A
- Rated current at 20 °C16.50 A
- Rated current at 25 °C16.20 A
- Rated current at 30 °C16.00 A
- Rated current at 35 °C15.80 A
- Rated current at 40 °C15.60 A
- Rated current at 50 °C15.20 A
- Rated current at 55 °C15.00 A
- Rated current at 60 °C14.80 A
- Correction factor for 2 devices side by side1.00
- Correction factor for 3 devices side by side0.95
- Correction factor for 4–5 devices side by side0.90
- Correction factor for 6 devices side by side0.85
- Thermal operation threshold (AC)1.13–1.45 A
- Rated short-circuit breaking capacity Icn (230 V AC, IEC 60898-1)6 kA
- Residual current typeA
- Ingress Protection (IP) classIP2X
- Rated short-circuit breaking capacity Icn AC (IEC 60898-1)6 kA
- Connection typeScrew terminal
- Rated insulation voltage Ui500 V
- Rated impulse withstand voltage Uimp4,000 V
- Maximum operating voltage240 V
- Rated operational voltage Ue240 V
- Overvoltage category (IEC 60947-1)3
- Total power loss at In5.20 W
- Frequency50 Hz
- Max. altitude2,000 m
- Energy limitation class I²t3
- Operating temperature–25 to +40 °C
- Storage/transport temperature–25 to +70 °C
- Electrical endurance2,000 cycles
- Mechanical endurance2,000 operations
- Conductor cross-section (flexible)1–16 mm²
- Conductor cross-section (rigid)1–25 mm²
- Input with screws (flexible conductor)1–16 mm²
- Input with screws (rigid conductor)1–25 mm²
- Output with screws (flexible conductor)1–16 mm²
- Output with screws (rigid conductor)1–25 mm²
- Input/output with screws (flexible conductor)1–16 mm²
- Input/output with screws (rigid conductor)1–25 mm²
- Nominal tightening torque2.10 Nm
- Top connection type (modular devices)Screw terminal
- Bottom connection type (modular devices)Biconnect
- Number of modules2
- Height83 mm
- Width35 mm
- Depth68 mm