Products catalog

  • Linear smoke detector FireBeam Blue (7-70 m, Bluetooth)

    Manufacturer
    Fireray
    • General
    • Supply Voltage12 to 30 Vdc normal
    • Supply Current5.5mA in all operational states
    • Supply Current13.5mA in fast commissioning
    • Temperature-10°C to +55°C
    • Humidity10 to 95% RH Non-condensing
    • Protection IndexIP65 when suitably mounted and terminated
    • Optical Wavelength870nm
    • Maximum Angular Alignment±5°
    • Maximum Angular Misalignment(static not auto-aligning)
    • Alarm Sensitivity Levels25% (1.25dB) to 50% (3dB) in 1% (0.05dB) increments (default 35% (1.87dB))
    • Alarm ConditionObscuration drops to below pre-defined sensitivity level. Time to Alarm Condition adjustable between 2 to 30 seconds in 1 second increments (default 10 seconds)
    • Alarm IndicationApp Status - FIRE, Head Red Flashing LED, Alarm Relay Change Over (CO) Contact, Rating 2A @ 30 VDC
    • Test / Reset FeaturesBeam test function with App, Alarm latching / auto-reset selectable (default auto-reset), Alarm reset in latching mode with App reset function, removing power for >5 seconds or momentarily apply >5 VDC to reset connections in Beam Head
    • Fault Sensitivity Level<4%
    • Fault ConditionObscuration drops to below the fault sensitivity level within 1 second, Power Down or Supply Voltage < 9 VDC, Commissioning modes, Pre-Alignment and Auto-Alignment, Beam turned off during Beam Maintenance, Time to Fault Condition adjustable, 2 to 60 seconds in 1 second increments (default 10 seconds)
    • Fault IndicationApp Status - FAULT, Head Yellow Flashing LED 1 Second, Fault Relay Change Over (CO) Contact Rating 2A @ 30 VDC
    • Normal ConditionObscuration level is above the Alarm sensitivity level, App Status - NORMAL, Programmable on/off, Head Green Flashing LED, Programmable on/off
    • Auto-Align / Beam Contamination CompensationAuto-align during normal operation if obscuration drops below 90% for the duration of the align time set (doesn't affect normal operating mode), Beam Contamination Compensation 4 hour monitoring. Compensation data available in the App