Products catalog

  • Isolator switch Hager SBN380 (3P, 80A, 400V, 3 modules)

    • General
    • Number of poles3
    • Neutral positionWithout neutral
    • Pole type3P
    • Rated current80 A
    • Rated conditional short-circuit current Icc (with gl-gG fuses)0.96 kA
    • Acceptable current rating (AC21 category A)80 A
    • Acceptable current rating (AC21 category B)80 A
    • Acceptable current rating (AC22 category A)80 A
    • Acceptable current rating (AC22 category B)80 A
    • Rated short-circuit making capacity Icm (415 V AC, IEC 60947-3)1.35 kA
    • Rated short-time withstand current Icw (1s, IEC 60947)0.96 kA
    • Nominal tightening torque3.60 Nm
    • Bottom connection type (modular devices)Screw terminal
    • Rated operational voltage Ue400 V AC
    • Rated insulation voltage Ui440 V
    • Rated impulse withstand voltage Uimp6,000 V
    • Number of modules3
    • Ingress Protection (IP) classIP20
    • Frequency50–60 Hz
    • Height83 mm
    • Width52.5 mm
    • Depth68 mm
    • Number of NO contacts3
    • Number of NC contacts0
    • Operating temperature–20 to +70 °C
    • Storage/transport temperature–40 to +80 °C
    • Cross-section flexible conductor6–35 mm²
    • Cross-section rigid conductor6–50 mm²
    • Mechanical endurance40,000 operations
    • Electrical durability (AC21, at nominal load)2,500 cycles
    • Electrical durability (AC22, at nominal load)2,500 cycles
    • Total power loss at In8.10 W
    • Power loss per pole at In2.70 W
    • Down connection alignment (modular devices)Aligned terminal
    • Top connection alignment (modular devices)Aligned terminal