Isolator switch Hager SBN380 (3P, 80A, 400V, 3 modules)
-
- General
- Number of poles3
- Neutral positionWithout neutral
- Pole type3P
- Rated current80 A
- Rated conditional short-circuit current Icc (with gl-gG fuses)0.96 kA
- Acceptable current rating (AC21 category A)80 A
- Acceptable current rating (AC21 category B)80 A
- Acceptable current rating (AC22 category A)80 A
- Acceptable current rating (AC22 category B)80 A
- Rated short-circuit making capacity Icm (415 V AC, IEC 60947-3)1.35 kA
- Rated short-time withstand current Icw (1s, IEC 60947)0.96 kA
- Nominal tightening torque3.60 Nm
- Bottom connection type (modular devices)Screw terminal
- Rated operational voltage Ue400 V AC
- Rated insulation voltage Ui440 V
- Rated impulse withstand voltage Uimp6,000 V
- Number of modules3
- Ingress Protection (IP) classIP20
- Frequency50–60 Hz
- Height83 mm
- Width52.5 mm
- Depth68 mm
- Number of NO contacts3
- Number of NC contacts0
- Operating temperature–20 to +70 °C
- Storage/transport temperature–40 to +80 °C
- Cross-section flexible conductor6–35 mm²
- Cross-section rigid conductor6–50 mm²
- Mechanical endurance40,000 operations
- Electrical durability (AC21, at nominal load)2,500 cycles
- Electrical durability (AC22, at nominal load)2,500 cycles
- Total power loss at In8.10 W
- Power loss per pole at In2.70 W
- Down connection alignment (modular devices)Aligned terminal
- Top connection alignment (modular devices)Aligned terminal