HIKVISION UPS DS-UPS06K-R/TJL(O-STD)/IEC (Rack/Tower, LCD, 6000VA/6000W)
-
HIKVISION UPS DS-UPS06K-R/TJL(O-STD)/IEC (Rack/Tower, LCD, 6000VA/6000W)
-
- Battery
- Battery TypeValve Regulated Lead Acid (VRLA)
- Charging Current (Max.)12A
- DC System Voltage (VDC)192/240Vdc (Settable)
- Expandable RuntimeYes, External battery pack: DS-UPSB09192A-R/TJ, or DS-UPSB09240A-R/TJ
- Typical Backup TimeView Runtime Graph
- Efficiency
- AC ModeUp to 95%
- Battery ModeUp to 93%
- Environment
- Altitude0~3000m (1000~3000m derating required)
- Humidity Range0~95% (Non - condensing)
- Noise Level≤50dB
- Operating Temperature0℃~40℃
- Storage Temperature-25℃~55℃
- Indicator
- AlarmBattery mode/Battery low voltage/Overload/Fault
- LCD displayInput voltage, Input frequency, Output voltage, Output frequency, Load percentage, Battery voltage, Inner temperature & Remaining battery backup time
- Input
- Input Frequency40~70Hz (50/60Hz Auto-Sensing)
- Input Voltage Range110~300Vac (110~300Vac@50% load/176~300Vac@100% load)
- Nominal Voltage208/220/230/240Vac
- PhaseSingle Phase
- Power factor≥0.99
- Output
- Crest factor3:1
- Harmonic distortion (THDv)≤1% Linear load
≤3% Non linear load
- Output FrequencyOnline mode:±1%/±2%/±4%/±5%/±10% of the rated frequency (Optional) Battery mode: (50/60±0.1%)Hz
- Output SocketsIEC version: Connecting terminal +IEC socket
US version: Connecting terminal+US socket panel
- Output Voltage208/220/230/240Vac
- Output WaveformPure Sinewave
- Power factor 1
- Transfer TimeAC mode to Bat.mode: 0ms Inverter to Bypass: 0ms
- Physical
- Dimension W x D x H (mm)440×621.5×86.5
- Net weight (kg)15.5
- Power
- UPS Capacity 6000 VA / 6000 W
- Standards
- EMCCE-EMC IEC/EN 62040-2 (IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8, IEC61000-4-11, IEC61000-2-2)
- SafetyCE-LVD IEC/EN 62040-1, IEC/EN 62477-1