  • DIN rail-mounted switching power supply 24V 100W 4.2A, MEAN WELL, HDR-100-24N

    Manufacturer
    Mean Well
    • General
    • ModelHDR-100-24N
    • DC Voltage24V
    • Rated Current4.2A
    • Current Range0 ~ 4.2A
    • Rated Power100.8W
    • Voltage Adjustment Range21.6 ~ 28V
    • Ripple & Noise (max.)150mVp-p
    • Voltage Tolerance±1.0%
    • Line Regulation±1.0%
    • Load Regulation±1.0%
    • Setup, Rise Time500ms, 30ms/230VAC; 500ms, 12ms/115VAC at full load
    • Hold Up Time (Typ.)30ms/230VAC; 12ms/115VAC at full load
    • Voltage Range85 ~ 264VAC, 120 ~ 370VDC
    • Frequency Range47 ~ 63Hz
    • Efficiency (Typ.)90%
    • AC Current (Typ.)1.6A/230VAC, 3A/115VAC
    • Inrush Current (Typ.)Cold start 50A/230VAC
    • Overload Protection110 ~ 150% rated output power, hiccup mode, recovers automatically after fault condition is removed
    • Over Voltage Protection28 ~ 33V, shut down output voltage, re-power on to recover
    • Working Temperature-30 ~ +70°C (Refer to "Derating Curve")
    • Working Humidity20 ~ 90% RH non-condensing
    • Storage Temperature, Humidity-40 ~ +85°C, 10 ~ 95% RH non-condensing
    • Temperature Coefficient±0.03%/°C (0 ~ 50°C)
    • Vibration10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Compliance to IEC60068-2-6
    • Withstand VoltageI/P-O/P: 4KVAC
    • Isolation ResistanceI/P-O/P: 100M Ohms / 500VDC / 25°C / 70% RH
    • Safety StandardsUL62368-1, UL508, TUV BS EN/EN61558-2-16, IEC62368-1, BSMI CNS15598-1, BS EN/EN61558-1, EAC TP TC 004
    • EMC EmissionBS EN/EN55032(CISPR32), CNS15936, Class B
    • EMC ImmunityEN61000-4-2, EN61000-4-3, EN61000-4-4, EN61000-4-5, EN61000-4-6, EN61000-4-8, EN61000-4-11
    • Operating AltitudeUp to 2000 meters
    • MTBF327.9K hrs min. (Telcordia SR-332), 856.5K hrs min. (MIL-HDBK-217F, 25°C)
    • Dimension (W*H*D)70*90*54.5mm
    • Packing0.27Kg; 48pcs/13.74Kg/0.96CUFT
    • InstallationDIN rail TS35/7.5 or TS35/15 mountable
    • LED IndicatorPower On