Products catalog

    • General
    • Cells per unit6
    • Voltage per unit12V
    • Nominal Capacity4Ah@20hour-rate to 1.75V per cell@25C
    • Weight1.25 kg (± 5%)
    • Internal resistance≤ 50 mΩ
    • TerminalF1, F2 (optional)
    • Max. discharge current40A (5 sec)
    • Short circuit current21A
    • Design life6-8 years
    • Max. charging current1.2A
    • Reference capacityC3 5.43Ah C5 6.11Ah C10 6.54Ah C20 7 Ah
    • Standby use capacity13.7V~13.9V @ 25°C Temperature Compensation: -3mV/'C/Cell
    • Cycle use voltage14.6 V~14.8V @ 25°C Temperature Compensation: -4mV/°C/Cell
    • Operating temperature rangeDischarge: -20'C~60C Charge: 0°C~50C Storage: -20'C~60°C
    • Normal operating temperature range25C+5C
    • Self dischargeRITAR Valve Regulated Lead Acid (VRLA) batteries can be stored for up to 6 months at 25°C and then recharging is recommended. Monthly Self-discharge ratio is less. than 3% at 25'C Please charge batteries before using
    • Container materialA.B.S. UL94-HB, UL94-V0 Optional