Products catalog

  • Battery (AGM) SSB SBL (40Ah, 12V, F13 M6, VRLA)

    Manufacturer
    SSB
    • General
    • Nominal voltage12 V
    • Nominal capacity42.4 Ah @ C20 to 1.75 V/cell, 40 Ah @ C10 to 1.80 V/cell
    • TechnologyAGM (Absorbent Glass Mat), VRLA (Valve Regulated Lead Acid)
    • Weight~ 13 kg
    • Design life time12 years (standby use), Long Life acc. Eurobat
    • Internal resistance~ 10 mΩ (fully charged)
    • Operating temperature rangeDischarge: -20°C to +60°C, Charge: 0°C to +50°C, Storage: -20°C to +60°C
    • Maximum discharge current400 A (5 seconds)
    • Short circuit current920 A
    • Maximum charging current12 A
    • Charging voltageStandby use: 13.6 – 13.8 VDC, Cycle use: 14.6 – 14.8 VDC
    • Self dischargeMonthly loss less than 3% at 25°C
    • Container materialABS UL94HB (optional UL94-V0)
    • Dimensions (L x W x H)198 ±2 mm x 166 ±2 mm x 169 ±2 mm
    • Total height169 ±2 mm
    • Terminal typesInternal thread M6 (breaking torque 8–10 Nm)
    • Standards metPN-EN 60896-21:2007, PN-EN 60896-22:2007, PN-EN 61056-1:2013, PN-EN 61056-2:2013, PN-E-83016:1999
    • CertificationsISO 9001, ISO 14001
    • ApplicationsUPS, Emergency Lighting, Fire Alarm Systems, Security Systems, Energy Utilities, DC Power Supply